The coverage of each dry chemical system monitor under § 154.1150 must not exceed:
- (a)10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);
- (b)30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);
- (c)40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);
- (d)An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or
- (e)An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).