46 CFR §154.345
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)An air lock may be used for access from a gas-dangerous zone on the weather deck to a gas-safe space.
- (b)Each air lock must:
- (1)Consist of two steel doors, at least 1.5 m (4.9 ft.) but not more than 2.5 m (8.2 ft.) apart, each gasketed and tight when tested with a fire hose at not less 207 kPa gauge (30 psig);
- (2)Have self-closing doors with no latches or other devices for holding them open;
- (3)Have an audible and visual alarm on both sides which are actuated when both door securing devices are in other than the fully closed position at the same time;
- (4)Have mechanical ventilation in the space between the doors from a gas-safe area;
- (5)Have a pressure greater than that of the gas-dangerous area on the weather deck;
- (6)Have the rate of air change in the space between the doors of at least 8 changes per hour; and
- (7)Have the space between the doors monitored for cargo vapor leaks under § 154.1350.
- (c)In addition to the requirements of paragraphs (a) and (b) of this section, no gas-safe space on a liquefied flammable gas carrier may have an air lock unless the space: