46 CFR §170.245
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Installation of foam must be approved by the OCMI.
- (b)If foam is used to comply with § 171.070(d), § 171.095(c), or § 173.063(e) of this subchapter, the following applies:
- (1)Foam may be installed only in void spaces that are free of ignition sources.
- (2)The foam must comply with NPFC MIL-P-21929B (incorporated by reference; see 46 CFR 170.015), including the requirements for fire resistance.
- (3)A submergence test must be conducted for a period of at least 7 days to demonstrate whether the foam has adequate strength to withstand a hydrostatic head equivalent to that which would be imposed if the vessel were submerged to its margin line.
- (4)The effective buoyancy at the end of the submergence test must be used as the buoyancy credit; however, in no case will a credit greater than 55 lbs per cubic foot (881 kilograms per cubic meter) be allowed.
- (5)The structure enclosing the foam must be strong enough to accommodate the buoyancy of the foam.
- (6)Piping and cables must not pass through foamed spaces unless they are within piping and cable trunks accessible from both ends.
- (7)Sample specimens must be prepared during installation and the density of the installed foam must be determined.
- (8)Foam may be installed adjacent to fuel tanks if the boundary between the tank and space has double continuous fillet welds.
- (9)MIL-P-21929B is incorporated by reference into this part.
- (10)The results of all tests and calculations must be submitted to the OCMI.
- (11)Blocked foam must—