46 CFR §181.400
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with § 181.410, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by paragraph (b) of this section:
- (1)A space containing propulsion machinery;
- (2)A space containing an internal combustion engine of more than 37.3 kW (50 hp);
- (3)A space containing an oil fired boiler;
- (4)A space containing machinery powered by gasoline or other fuels having a flash point of 43.3 °C (110 °F) or lower;
- (5)A space containing a fuel tank for gasoline or any other fuel having a flash point of 43.3 °C (110 °F) or lower;
- (6)A space containing combustible cargo or ship's stores inaccessible during the voyage (in these types of spaces only carbon dioxide, and not Halon, systems will be allowed);
- (7)A paint locker; and
- (8)A storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater).
- (b)Alternative system types and exceptions to the requirements of paragraph (a) of this section are:
- (1)A fixed gas fire extinguishing system, which is capable of automatic discharge upon heat detection, may only be installed in a normally unoccupied space with a gross volume of not more than 170 cubic meters (6,000 cubic feet);
- (2)A pre-engineered fixed gas fire extinguishing system must be in compliance with § 181.420 of this part and may only be installed in a normally unoccupied machinery space, a paint locker, or a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater), with a gross volume of not more than 57 cubic meters (2,000 cubic feet);
- (3)A 40-B portable fire extinguisher installed outside the space may be substituted for a fixed gas fire extinguishing system in a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater) or a paint locker, with a volume of not more that 5.7 cubic meters (200 cubic feet);
- (4)A space which is so open to the atmosphere that a fixed gas fire extinguishing system would be ineffective, as determined by the cognizant OCMI, is not required to have a fixed gas fire extinguishing system; and
- (5)Where the amount of carbon dioxide gas required in a fixed fire extinguishing system can be supplied by one portable extinguisher or a semi-portable extinguisher, such an extinguisher may be used subject to the following:
- (c)All griddles, broilers, and deep fat fryers must be fitted with a grease extraction hood in compliance with § 181.425 of this subchapter.
- (d)An enclosed vehicle space must be fitted with an automatic sprinkler system that meets the requirements of part 76 of this chapter.
- (e)A partially enclosed vehicle space must be fitted with a manual sprinkler system that meets the requirements of part 76 of this chapter.