46 CFR §182.480
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)A flammable vapor detection system required by § 182.410(c) must meet UL 1110 (incorporated by reference; see 46 CFR 175.600) or be approved by an independent laboratory.
- (b)Procedures for checking the proper operation of a flammable vapor detection system must be posted at the primary operating station. The system must be self-monitoring and include a ground fault indication alarm.
- (c)A flammable vapor detection system must be operational for 30 seconds prior to engine startup and continue sensing the entire time the engine is running.
- (d)A flammable vapor detection system must provide a visual and audible alarm at the operating station.
- (e)A sensor must be located above the expected bilge water level in the following locations:
- (f)A flammable vapor detection system must be installed so as to permit calibration in a vapor free atmosphere.
- (g)Electrical connections, wiring, and components for a flammable vapor detection system must comply with part 183 of this chapter.
- (h)An operation and maintenance manual for the flammable vapor detection system must be kept onboard.