46 CFR §28.360
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Each electrical distribution system which has a neutral bus or conductor must have the neutral bus or conductor grounded.
- (b)A grounded electrical distribution system must have only one connection to ground. This ground connection must be at the switchboard or, on a nonmetallic vessel, at the common ground point.