  1. (a)Piping for instruments, control, and sampling must comply with paragraph 122.3 of ASME B31.1 (incorporated by reference; see § 56.01-2) except that:
    1. (1)Soldered type fittings may not be used.
    2. (2)The outside diameter of takeoff connections may not be less than 0.840 inches for service conditions up to 900 psig or 800 °F, and 1.050 inches for conditions that exceed either of these limits.