46 CFR §63.15-3
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Firing of an automatic auxiliary boiler by natural gas is prohibited unless specifically approved by the Marine Safety Center.
- (b)Heated heavy fuel oil may be used provided the heaters are equipped with a high temperature limiting device that shuts off the heating source at a temperature below the flashpoint of the oil and is manually reset. When a thermostatically-controlled electric oil heater and a level device is used, it must meet the requirements of subpart 111.85 of this chapter.
- (c)The fuel oil service pump and its piping system must be designed in accordance with § 56.50-65 of this subchapter. All materials must meet the requirements of subpart 56.60 of this subchapter. The use of cast iron or malleable iron is prohibited.
- (d)The fuel oil service system (including the pump) must meet the pressure classification and design criteria found in table 1 to § 56.04-2 of this subchapter.
- (e)When properly selected for the intended service, fuel pumps meeting the performance and test requirements of UL 343 (incorporated by reference, see § 63.05-1) meet the requirements of this section.