46 CFR §76.27-20
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Audible alarms must generate sound pressure levels as set forth in 46 CFR 161.002 and must:
- (1)Be at least 75 dBA as measured at the sleeping position in cabins;
- (2)Be at least 10 dBA above ambient noise levels existing during normal operation with the ship under way in moderate weather when measured at a point 5 feet (1.5 meters) above the finished floor and at least 3 feet (1 meter) from the source;
- (3)Not exceed 120 dBA; and
- (4)The sound pressure level must be measured in the third octave band about the fundamental frequency.
- (b)Visual alarms must generate light of an intensity and period as set forth in 46 CFR 161.002.
- (c)All audible and visual alarms must be audible and visible throughout the spaces they are intended to alert.