- (a)The fire detection system must be divided into separate zones to restrict the area covered by any particular alarm signal.
- (b)The fire detection zone must not include spaces in more than one main vertical zone, except on cabin balconies.
- (c)The fire detection zone must not include spaces on more than one deck, except—
- (1)Adjacent and communicating spaces on different decks at the ends of the vessel having a combined ceiling area of not more than 3,000 sq ft;
- (2)Isolated rooms or lockers in such spaces as mast houses or wheelhouse tops, which are easily communicable with the area of the fire detection circuit to which they are connected; and
- (3)Systems with addressable detectors and manual alarm stations that can have their status individually determined.
- (d)Any fire detection zone with non-addressable detectors and manual pull stations must not contain more than 25 protected rooms or spaces.