46 CFR §95.15-30
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)A protected space must be fitted with an approved audible alarm if:
- (b)The alarm must:
- (1)Sound automatically and audibly for at least 20 seconds before carbon dioxide is discharged into the space;
- (2)Be conspicuously and centrally located and be marked as required by 46 CFR 97.37-9; and
- (3)Use stored gas power provided by the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.
- (c)For systems installed on or after July 1, 1957, alarms are mandatory only for systems required to be fitted with a delayed discharge.