46 CFR §95.16-25
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)A check valve must be provided between each cylinder and manifold or distribution piping. The valve must be permanently marked to indicate the direction of flow.
- (b)If the same cylinder is used to protect more than one space, normally, closed stop valves must be provided to direct the agent into each protected space.
- (c)Each cylinder must be fabricated, tested, and marked in accordance with 46 CFR 147.60(b) and 49 CFR part 180.
- (d)The cylinders in a common manifold must be: