- (a)Each system protecting a space with greater than 6,000 cubic feet gross volume or a space less than 6,000 cubic feet gross volume without a suitable horizontal escape route must have a pneumatic pre-discharge alarm and time delay.
- (b)The pre-discharge alarm must:
- (1)Sound for the duration of the time delay;
- (2)Be conspicuously and centrally located in the protected space and marked as required by 46 CFR 97.37-9;
- (3)Depend on the extinguishing agent, gas from a pilot cylinder, or a nitrogen cylinder specifically provided to power the alarm for its source of power; and
- (4)Be audible over running machinery.