Appendix I to Subpart D of Part 18
Open Table
LIST OF TABLES
| Table No. |
Title |
| 1 |
Portable power cable ampacities—600 volts. |
| 2 |
Portable cord ampacities—600 volts. |
| 3 |
Portable power cable ampacities—601 to 5,000 volts. |
| 4 |
Normal diameter of round cables with tolerances in inches—600 volts. |
| 5 |
Nominal dimension of flat cables with tolerances in inches—600 volts. |
| 6 |
Nominal diameter of heavy jacketed cords with tolerances in inches—600 volts. |
| 7 |
Nominal diameter of three-conductor portable power cables with tolerances in inches—601 to 5,000 volts. |
| 8 |
Fuse ratings or instantaneous settings of circuit breakers for short-circuit protection of portable cables. |
| 9 |
Specifications for portable cables longer than 500 feet. |
| 10 |
High voltage trailing cable ampacities and outside diameters. |
Open Table
Table 1—Portable Power Cable Ampacities—600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature—40 °C. Ambient)
| Conductor size—AWG or MCM |
Single conductor |
2-conductor, round or flat |
3-conductor, round or flat |
4-conductor |
5-conductor |
6-conductor |
| 8 |
45 |
40 |
35 |
30 |
25 |
20 |
| 6 |
60 |
50 |
50 |
40 |
35 |
30 |
| 4 |
85 |
70 |
65 |
55 |
45 |
35 |
| 3 |
95 |
80 |
75 |
65 |
55 |
45 |
| 2 |
110 |
95 |
90 |
75 |
65 |
55 |
| 1 |
130 |
110 |
100 |
85 |
75 |
65 |
| 1/0 |
150 |
130 |
120 |
100 |
90 |
80 |
| 2/0 |
175 |
150 |
135 |
115 |
105 |
95 |
| 3/0 |
205 |
175 |
155 |
130 |
120 |
110 |
| 4/0 |
235 |
200 |
180 |
150 |
140 |
130 |
| 250 |
275 |
220 |
200 |
160 |
|
|
| 300 |
305 |
240 |
220 |
175 |
|
|
| 350 |
345 |
240 |
235 |
190 |
|
|
| 400 |
375 |
280 |
250 |
200 |
|
|
| 450 |
400 |
300 |
270 |
215 |
|
|
| 500 |
425 |
320 |
290 |
230 |
|
|
Open Table
Table 2—Portable Cord Ampacities—600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature—40 °C. Ambient)
| Conductor size—AWG |
1-3 conductor |
4-6 conductor |
7-9 conductor |
| 14 |
15 |
12 |
8 |
| 12 |
20 |
16 |
11 |
| 10 |
25 |
20 |
14 |
Open Table
Table 3—Portable Power Cable Ampacities—601 to 5,000 Volts (Amperes Per Conductor Based on 75 °C. Copper Temperature—40 °C. Ambient)
| Conductor size—AWG or MCM |
3-conductor types G-GC and SIIC-GC 2,000 volts |
3-conductor type SHD-GC 2,001-5,000 volts |
| 6 |
65 |
65 |
| 4 |
85 |
85 |
| 3 |
100 |
100 |
| 2 |
115 |
115 |
| 1 |
130 |
130 |
| 1/0 |
145 |
145 |
| 2/0 |
170 |
170 |
| 3/0 |
195 |
195 |
| 4/0 |
220 |
220 |
| 250 |
245 |
245 |
| 300 |
275 |
275 |
| 350 |
305 |
305 |
Open Table
Table 4—Nominal Diameters of Round Cables With Tolerances in Inches—600 Volts
| Conductor size—AWG or MCM |
Single conductor |
2-conductor |
3-conductor |
4-conductor—Types W & G |
5-conductor—Types W & G |
6-conductor |
| Types W & G twisted |
Type PG, 2 power |
Type PCG, 3 power, ground |
Types W & G |
Type PG, 3 power, ground |
Type PCG, 3 power, 2 control, ground |
Type w |
Tolerance |
| 8 |
0.44 |
0.81 |
0.84 |
0.94 |
0.91 |
0.93 |
1.03 |
0.99 |
1.07 |
1.18 |
±0.03 |
| 6 |
.51 |
.93 |
.93 |
.98 |
1.01 |
1.03 |
1.18 |
1.10 |
1.21 |
1.31 |
±.03 |
| 4 |
.57 |
1.08 |
1.08 |
1.10 |
1.17 |
1.20 |
1.29 |
1.27 |
1.40 |
1.52 |
±.03 |
| 3 |
.63 |
1.17 |
1.17 |
1.20 |
1.24 |
1.27 |
1.31 |
1.34 |
1.48 |
1.61 |
±.03 |
| 2 |
.66 |
1.27 |
1.27 |
1.29 |
1.34 |
1.34 |
1.39 |
1.48 |
1.61 |
1.75 |
±.03 |
| 1 |
.74 |
1.44 |
1.44 |
1.44 |
1.51 |
1.52 |
1.52 |
1.68 |
1.88 |
2.05 |
±.03 |
| 1/0 |
.77 |
1.52 |
1.52 |
1.52 |
1.65 |
1.68 |
1.68 |
1.79 |
1.96 |
2.13 |
±.04 |
| 2/0 |
.82 |
1.65 |
1.65 |
1.65 |
1.75 |
1.79 |
1.79 |
1.93 |
2.13 |
2.32 |
±.04 |
| 3/0 |
.87 |
1.77 |
1.77 |
1.77 |
1.89 |
1.93 |
1.93 |
2.07 |
2.26 |
2.49 |
±.05 |
| 4/0 |
.93 |
1.92 |
1.92 |
1.92 |
2.04 |
2.13 |
2.13 |
2.26 |
2.46 |
2.71 |
±.05 |
| 250 |
1.03 |
2.16 |
2.16 |
2.16 |
2.39 |
2.39 |
2.39 |
2.66 |
|
|
±.06 |
| 300 |
1.09 |
2.32 |
|
|
2.56 |
|
|
2.84 |
|
|
±.06 |
| 350 |
1.15 |
2.43 |
|
|
2.68 |
|
|
2.98 |
|
|
±.06 |
| 400 |
1.20 |
2.57 |
|
|
2.82 |
|
|
3.14 |
|
|
±.06 |
| 450 |
1.26 |
2.67 |
|
|
2.94 |
|
|
3.26 |
|
|
±.06 |
| 500 |
1.31 |
2.76 |
|
|
3.03 |
|
|
3.40 |
|
|
±.06 |
Open Table
Table 5—Nominal Dimensions of Flat Cables With Tolerances in Inches—600 Volts
| Conductor size—AWG |
2-conductor |
3-conductor—Type G |
| Type W |
Type G |
Major |
Minor |
| Major |
Minor |
Major |
Minor |
O.D. |
Tolerance |
O.D. |
Tolerance |
| O.D. |
Tolerance |
O.D. |
Tolerance |
O.D. |
Tolerance |
O.D. |
Tolerance |
| 8 |
0.84 |
±0.04 |
0.51 |
±0.03 |
|
|
|
|
|
|
|
|
| 6 |
.93 |
±.04 |
.56 |
±.03 |
1.02 |
±.04 |
0.56 |
±.03 |
1.65 |
±0.06 |
0.67 |
±0.05 |
| 4 |
1.05 |
±.04 |
.61 |
±.03 |
1.15 |
±.04 |
.61 |
±.03 |
1.85 |
±.06 |
.75 |
±.05 |
| 3 |
1.14 |
±.04 |
.68 |
±.03 |
1.26 |
±.04 |
.68 |
±.03 |
1.99 |
±.06 |
.77 |
±.05 |
| 2 |
1.24 |
±.04 |
.73 |
±.03 |
1.35 |
±.04 |
.73 |
±.06 |
2.10 |
±.06 |
.81 |
±.05 |
| 1 |
1.40 |
±.04 |
.81 |
±.03 |
1.55 |
±.04 |
.81 |
±.03 |
2.43 |
±.06 |
.97 |
±.05 |
| 1/0 |
1.51 |
±.04 |
.93 |
±.03 |
1.67 |
±.04 |
.93 |
±.03 |
|
|
|
|
| 2/0 |
1.63 |
±.04 |
.99 |
±.03 |
1.85 |
±.04 |
.99 |
±.03 |
|
|
|
|
| 3/0 |
1.77 |
±.04 |
1.03 |
±.03 |
2.00 |
±.04 |
1.03 |
±.03 |
|
|
|
|
| 4/0 |
1.89 |
±.04 |
1.10 |
±.03 |
2.10 |
±.04 |
1.10 |
±.03 |
|
|
|
|
Open Table
Table 6—Nominal Diameters of Heavy Jacketed Cords With Tolerances In Inches—600 Volts
| Conductor size—AWG |
2-conductor |
3-conductor |
4-conductor |
5-conductor |
6-conductor |
7-conductor |
| Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
| 14 |
0.64 |
±0.02 |
0.67 |
±0.02 |
0.71 |
±0.02 |
0.78 |
±0.03 |
0.83 |
±0.03 |
0.89 |
±0.03 |
| 12 |
.68 |
±.02 |
.72 |
±.03 |
.76 |
±.03 |
.83 |
±.03 |
.89 |
±.03 |
.98 |
±.03 |
| 10 |
.73 |
±.03 |
.80 |
±.03 |
.84 |
±.03 |
.90 |
±.03 |
1.00 |
±.03 |
1.07 |
±.03 |
Open Table
Table 7—Nominal Diameters of Three-Conductor Portable Power Cables With Tolerances in Inches—601 to 5,000 Volts
| Conductor size—AWG or MCM |
Type G-GC (nonshielded) 2,000 volts |
Type SHC-GC (shielded overall) 2,000 volts |
Type SHD-GC (individually shielded power conductors) 2,001-3,000 volts |
Type SHD-GC (individually shielded power conductors) 3,001-5,000 volts |
| Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
Diameter |
Tolerance |
| 6 |
1.25 |
+ 0.10, −0.06 |
1.39 |
+ 0.11, −0.07 |
1.62 |
+ 0.13, −0.08 |
1.78 |
+ 0.14, −0.09 |
| 4 |
1.40 |
+ .11, −.07 |
1.55 |
+ .12, −.08 |
1.77 |
+ .14, −.09 |
1.90 |
+ .15, −.10 |
| 3 |
1.48 |
+ .12, −.07 |
1.62 |
+ .13, −.08 |
1.84 |
+ .15, −.09 |
1.98 |
+ .16, −.10 |
| 2 |
1.55 |
+ .12, −.08 |
1.71 |
+ .14, −.09 |
1.92 |
+ .15, −.10 |
2.09 |
+ .17, −.11 |
| 1 |
1.74 |
+ .14, −.09 |
1.89 |
+ .15, −.09 |
2.04 |
+ .16, −.10 |
2.18 |
+ .17, −.11 |
| 1/0 |
1.84 |
+ .15, −.09 |
2.02 |
+ .16, −.10 |
2.18 |
+ .17, −.11 |
2.34 |
+ .19, −.12 |
| 2/0 |
1.99 |
+ .16, −.10 |
2.16 |
+ .17, −.11 |
2.29 |
+ .18, −.12 |
2.46 |
+ .20, −.12 |
| 3/0 |
2.12 |
+ .17, −.11 |
2.30 |
+ .18, −.11 |
2.45 |
+ .20, −.12 |
2.62 |
+ .21, −.13 |
| 4/0 |
2.30 |
+ .18, −.12 |
2.48 |
+ .20, −.12 |
2.62 |
+ .21, −.13 |
2.76 |
+ .22, −.14 |
| 250 |
2.46 |
+ .20, −.12 |
2.70 |
+ .22, −.13 |
|
|
|
|
| 300 |
2.63 |
+ .21, −.13 |
2.84 |
+ .23, −.14 |
|
|
|
|
| 350 |
2.75 |
+ .22, −.14 |
2.97 |
+ .24, −.15 |
|
|
|
|
Open Table
Table 8—Fuse Ratings or Instantaneous Setting of Circuit Breakers for Short-Circuit Protection of Portable Cables and Cords
| Conductor size—AWG or MCM |
Ohms/1,000 ft. at 25 °C. |
Maximum allowable fuse rating (amperes) |
Maximum allowable circuit breaker instantaneous setting (amperes) 1
|
| 14 |
2.62 |
20 |
50 |
| 12 |
1.65 |
30 |
75 |
| 10 |
1.04 |
40 |
150 |
| 8 |
.654 |
80 |
200 |
| 6 |
.410 |
100 |
300 |
| 4 |
.259 |
200 |
500 |
| 3 |
.205 |
250 |
600 |
| 2 |
.162 |
300 |
800 |
| 1 |
.129 |
375 |
1,000 |
| 1/0 |
.102 |
500 |
1,250 |
| 2/0 |
.081 |
|
1,500 |
| 3/0 |
.064 |
|
2,000 |
| 4/0 |
.051 |
|
2,500 |
| 250 |
.043 |
|
2,500 |
| 300 |
.036 |
|
2,500 |
| 350 |
.031 |
|
2,500 |
| 400 |
.027 |
|
2,500 |
| 450 |
.024 |
|
2,500 |
| 500 |
.022 |
|
2,500
|
|
1 Higher circuit-breaker settings may be permitted for special applications when justified. |
Open Table
Table 9—Specifications for Portable Cables Longer Than 500 Feet 1
| Conductor size—AWG or MCM |
Max. allowable length (feet) |
Normal ampacity at 60 °C. copper temperature (40 °C. ambient) |
Resistance at 60 °C. copper temperature (ohms) |
| 6 |
550 |
50 |
0.512 |
| 4 |
600 |
70 |
.353 |
| 3 |
650 |
80 |
.302 |
| 2 |
700 |
95 |
.258 |
| 1 |
750 |
110 |
.220 |
| 1/0 |
800 |
130 |
.185 |
| 2/0 |
850 |
150 |
.157 |
| 3/0 |
900 |
175 |
.130 |
| 4/0 |
1,000 |
200 |
.116 |
| 250 |
1,000 |
220 |
.098 |
| 300 |
1,000 |
240 |
.082 |
| 350 |
1,000 |
260 |
.070 |
| 400 |
1,000 |
280 |
.061 |
| 450 |
1,000 |
300 |
.054 |
| 500 |
1,000 |
320 |
.050
|
|
1 Fuses shall not be used for short-circuit protection of these cables. Circuit breakers shall be used with the instantaneous trip settings not to exceed the values given in Table 8. |
Open Table
Table 10—High Voltage Trailing Cable Ampacities and Outside Diameters
| Power conductor |
Ampacity * |
Outside diameter ** (inches) |
| Size AWG or kcmil |
Amperes per conductor |
SHD-GC 2001 to 5000 volts |
SHD-CGC 2001 to 5000 volts |
SHD-PCG 2001 to 5000 volts |
| 6 |
93 |
1.56 |
1.62 |
|
| 4 |
122 |
1.68 |
1.73 |
|
| 3 |
140 |
1.78 |
1.82 |
1.94 |
| 2 |
159 |
1.87 |
1.91 |
2.03 |
| 1 |
184 |
1.95 |
1.98 |
2.12 |
| 1/0 |
211 |
2.08 |
2.10 |
2.26 |
| 2/0 |
243 |
2.20 |
2.20 |
2.40 |
| 3/0 |
279 |
2.36 |
2.36 |
2.58 |
| 4/0 |
321 |
2.50 |
2.50 |
2.76 |
| 250 |
355 |
2.69 |
2.69 |
|
| 300 |
398 |
2.81 |
2.81 |
|
| 350 |
435 |
2.95 |
2.95 |
|
| 500 |
536 |
3.31 |
3.31
|
|
| * These ampacities are based on single isolated conductor in air, operated with open-circuited shield for a 90 °C conductor temperature and an ambient temperature of 40 °C.
|
| ** Tolerances for the outside diameter are + 8%/−5%. |
[33 FR 4660, Mar. 19, 1968; 33 FR 6345, Apr. 26, 1968, as amended at 42 FR 8373, Feb. 10, 1977; 75 FR 17549, Apr. 6, 2010; 75 FR 20918, Apr. 22, 2010]