As stated in §63.1566(c)(1), you shall meet each requirement in the following table that applies to you.

Open Table
For each applicable process vent for a new or existing catalytic reforming unit .  .  . If you use .  .  . For this operating limit .  .  . You shall demonstrate continuous compliance during initial catalyst depressuring and purging operations by .  .  .
1. Option 1 Flare The flare pilot light must be present at all times and the flare must be operating at all times that emissions may be vented to it On and after January 30, 2019, meeting the requirements of §63.670. Prior to January 30, 2019, collecting flare monitoring data according to §63.1572 and recording for each 1-hour period whether the monitor was continuously operating and the pilot light was continuously present during each 1-hour period, or meeting the requirements of §63.670.
2. Option 2 a. Thermal incinerator boiler or process heater with a design input capacity under 44 MW or boiler or process heater in which not all vent streams are not introduced into the flame zone Maintain the daily average combustion zone temperature above the limit established during the performance test Collecting, the hourly and daily temperature monitoring data according to §63.1572; and maintaining the daily average combustion zone temperature above the limit established during the performance test.
    b. No control device Operate at all times according to your operation, maintenance, and monitoring plan regarding minimum purging conditions that must be met prior to allowing uncontrolled purge releases Recording information to document compliance with the procedures in your operation, maintenance, and monitoring plan.

[70 FR 6954, Feb. 9, 2005, as amended at 80 FR 75306, Dec. 1, 2015]


Tried the LawStack mobile app?

Join thousands and try LawStack mobile for FREE today.

  • Carry the law offline, wherever you go.
  • Download CFR, USC, rules, and state law to your mobile device.