46 CFR §162.161-4
Verified against eCFR.gov as of June 20, 2026View official text on eCFR.gov ↗
- (a)Each pressure vessel must comply with 46 CFR 147.60(a) and (b).
- (b)Each system must be capable of operation without an external power source.
- (c)Manual actuation for the system must be by mechanical or pneumatic means.
- (d)Automatically actuated systems must be released by pneumatic or fusible element detection systems.
- (e)Each system installed with the extinguishing agent cylinders stored inside a protected space of 6,000 cubic feet or less must use automatic actuation as the primary means of actuation and have a remote backup manual mechanical actuator.
- (f)Each container charged with nitrogen must have a pressure gauge.